Phone
+65 9825 7795
Quality & Compliance:
The Ex product will follow the ATEX standard EN 60079 series and EN 1834 series ,and will give a《DECLARATION OF CONFORMITY》which is signed by the manufacturer according to the ATEX Standard EN 1834-1.
MODEL | EADG60-EX2 |
COMPLETE MACHINE | |
Explosion-proof Mark | II 3G IIB T3 Gc |
Hazardous Zone | ZONE 2 |
Certificate | 《Declaration of conformity》 |
Typical generating set output (0.8 pf 25ºC) | 60KVA 380V /50HZ |
Max. Working Angle | 15° |
75 | |
Machine Weight (kg) | 2500 (dry) |
Dimensions: L x W x H mm | 3412X2200X2256 |
Fuel tank | >300L |
DIESEL ENGINE | |
Manufacturer | CUMMINS |
Model | 6BT5.9-G2 |
Governed Speed (rpm) | 1500/1800 |
Prime Power (kW) | 96kW@1500rpm |
Displacement (L) | 5.9 |
No. of cylinders | 6 |
Engine Oil Capacity (L) | 18 |
Electrical System Voltage (V) | 24 |
Rated Capacity of Battery | 120Ah/ea |
GENERATORS | |
Manufacturer | Kingway OEM |
Explosion-proof Mark | II 3G Ex nA IIB T3 IP54 |
Certificate number | 《Declaration of conformity》 |
Hazardous Zone | ZONE 2 |
Ambient temperature | -25℃~ +60℃ |
Altitude | ≤1000M |
Rated Voltage | 380V(50HZ) |
Rated Frequency | 50HZ |
Rated REV | 1500RPM |
Power Factor | 0.8 LAG |
Operation | Continuous (S1) |
IP Grade | IP66 |
Controller | ComAp MRS16 |
Diesel driven generator sets for applications in Hazardous Area ( Zone 2 ) mounted in the DNV certified 2.7-1 Skid frame enclosure producing 250KVA @ 0...
Diesel driven generator sets for applications in Hazardous Area ( Zone 2 ) mounted in the DNV certified 2.7-1 Skid frame enclosure producing 100KVA @ 0...
100KVA Zone 2 Explosion Proof Generator...
100KVA ATEX Zone 2 Explosion Proof Generator...